Stranded Class 2 bare copper wire to BS EN 60228 cables are non insulated and non sheathed soft drawn copper to BS6360/81. Stranded bare soft or annealed copper conductors are recommended for use as neutrals, in circuit ground connections as well as machinery and equipment grounding systems. Soft copper may be used for transformer drop leads or other non-tension hook-up jumpers.
Product Code | Dimension and Weights | Electrical Properties | |||||||||
Nominal Cross Section | Overall Diemeter ( ~ ) |
Net Weight ( ~ ) |
Standart Lenght | Max. Dc Conductor Resistance at 20◦ C | Current Carrying Capacity | ||||||
In Ground at 20° C | On Air at 30° C | ||||||||||
28-66000001 | 1×6 mm² | 3 | 58 | 1000 | 3.08 | 3.08 | - | ||||
28-66000002 | 1×10 mm² | 4.2 | 96 | 1000 | 1.83 | 1.83 | - | ||||
28-66000003 | 1×16 mm² | 5.1 | 154 | 1000 | 1.15 | 1.15 | - | ||||
28-66000004 | 1×25 mm² | 5.9 | 240 | 1000 | 0.727 | 0.727 | - | ||||
28-66000005 | 1×35 mm² | 7.8 | 336 | 1000 | 0.524 | 0.524 | - | ||||
28-66000006 | 1×50 mm² | 8.8 | 480 | 1000 | 0.387 | 0.387 | - | ||||
28-66000007 | 1×70 mm² | 9.8 | 672 | 500 | 0.268 | 0.268 | - | ||||
28-66000008 | 1×95 mm² | 12.5 | 912 | 500 | 0.193 | 0.193 | - | ||||
28-66000009 | 1×120 mm² | 12.8 | 1152 | 500 | 0.153 | 0.153 | - | ||||
28-66000010 | 1×150 mm² | 14.4 | 1440 | 500 | 0.124 | 0.124 | - | ||||
28-66000011 | 1×185 mm² | 16.1 | 1776 | 500 | 0.0991 | 0.0991 | - | ||||
28-66000012 | 1×240 mm² | 19.8 | 2304 | 500 | 0.0754 | 0.0754 | - | ||||
28-66000013 | 1×300 mm² | 20.6 | 2800 | 500 | 0.0601 | 0.0601 | - | ||||
28-66000014 | 1×400 mm² | 26.4 | 3750 | 500 | 0.047 | 0.047 | - |